ADAM 4018P

ADAM Remote Data Acquisition Module - 8 Channels of 16-bit A/D with Thermocouple Support, Modbus Compliant

Qty   Price (with options selected)
Shipping: Call for Availability
 Features
System BusRS-422/485 serial
Number of Channels8
A/D Converter Resolution16-bit
Max. A/D Speed (throughput)10Hz
You Can Easily Panel-Mount, DIN Rail-Mount, or Piggyback-Mount Modules Modules Communicate Over a Single Twisted Pair
 
Introduction

There are four ADAM™ modules that accept thermocouple inputs. All four accept J, K, T, E, R, S, & B-type thermocouples, and all provide 3000VDC isolation.

  • ADAM 4011 has one differential input with 2 megohms impedance.
  • ADAM 4019 has 8 differential inputs with 20 megohms impedance, and it accepts Modbus inputs.
  • ADAM 4018 has 6 differential plus 2 single-ended inputs with 20 megohms impedance.
  • ADAM 4018M adds a data logger to ADAM 4018.

ADAM modules use a single twisted pair of wires to transmit and receive data. All module commands are issued in printable ASCII characters. You can easily panel-mount, DIN-rail-mount, or piggyback-mount modules. Removable screw terminal connectors make wiring and field maintenance easy.

Modules accept any unregulated power source between 10 and 30 VDC. A watchdog timer supervisory function automatically resets the modules in the event of system failure.

Our CyMOD series of modules has been designed with state-of-the art surface-mount technology to be completely hardware and software compatible with the ADAM series, at a somewhat lower cost. CM 4011 and CM 4018 are thermocouple modules that parallel the similarly numbered ADAM modules.

  Less Detail  More Detail
Product Information
System Bus RS-422/485 serial
Bus Information Baud Rate, Max. 115.2 kbps
Mounting Configuration Desktop / benchtop
Wall-mount
External module
DIN-rail mount
Direct Sensor Input Thermocouple
On-Board FIFO Memory Buffer 1 sample per channel
On-board Microprocessor Yes
Analog Input Channels
Number of Channels 8
Differential Channels 8
A/D Converter Resolution 16-bit
Max. A/D Speed (throughput) 10Hz
Typ. A/D Speed (throughput) 10Hz
A/D Converter Settling Time 100ms
Bandwidth 15.72Hz
A/D Speed/Bandwidth Details 13.1Hz @ 50Hz; 15.72Hz @ 60Hz
Accuracy Relative Accuracy ±0.01% for voltage input
Zero Drift ±3mV/°C
Noise CMRR (Common Mode Rejection Ratio) 92dB min.
Input Impedance 20MΩ
Input Protection Protected against voltages to +/-35VDC, max. with power on
A/D Special Features

Microprocessor has seven basic functions:

  • Linearization of T/C (Thermocouples)
  • Communication software and command set
  • Calibration software
  • Alarm monitoring
  • Event counting
  • Management of the EEPROM device that holds the system parameters
  • Data transformation
Input Ranges
Current Input Ranges 4 to 20mA
Thermocouple Support Thermocouple Inputs J-type thermocouple
K-type thermocouple
T-type thermocouple
E-type thermocouple
R-type thermocouple
S-type thermocouple
B-type thermocouple
J-type Range Supported 32°F....1400°F (0°C....760°C)
K-type Range Supported 32°F....2498°F (0°C....1370°C)
T-type Range Supported -148°F....752°F (-100°C....400°C)
E-type Range Supported 32°F....1832°F (0°C....1000°C)
R-type Range Supported 932°F....3182°F (500°C....1750°C)
S-type Range Supported 932°F....3182°F (500°C....1750°C)
B-type Range Supported 932°F....3272°F (500°C....1800°C)
A/D Range Selection Software
Input Range Details Software configurable for T/C, low-level voltage or mA inputs
Isolation, Field-to-Logic 3000VDC
Trigger Modes
Triggering Type(s) Supported Software trigger (software-controlled trigger)
Software
Software Included - Features Setup and utility software included
Operating System Compatibility Windows NT
Windows 2000
Windows 98
Windows 95
Software Compatibility Labtech NOTEBOOK®
DASYLab®
GENIDaq
Labtech CONTROL®
Labtech NOTEBOOKpro®
Labtech CONTROLpro®
DASYLab Lite®
LabVIEW®
Cables and Connectors
Connector #1 Quantity 20
Type Screw terminals as removable (lift-off) terminal strips
Location On module
Connector & Cabling Details 4 terminals for RS-422/485 data, DC supply voltage, and ground.
One terminal can reset module to default address/baud rate.
Other 15 terminals are used for A/D input channels and analog ground.
Construction
Construction Material Impact resistant ABS plastic
Power
Power Consumption (typical) 0.8W
Power Supply Notes Power Requirements: Unregulated +10 to +30VDC
System Monitoring
Watchdog Timer Included Yes
Watchdog Timer Intervals 100ms to 100 seconds in 0.1-second intervals
Environmental Specifications
Operating Temperature 32°F....158°F (0°C....70°C)
Relative Humidity, noncondensing 0%....95%
Safety & Standards Compliance
Safety/Approvals Meets CE standards
Dimensions
Width 2.76" (70mm)
Height 1.65" (42mm)
Depth 4.83" (122.6mm)
Dimension Details Height: 1" (25mm) without removable DIN-rail mounting bracket. Wall-mount bracket (included) adds 6.2mm (31.2mm height w/steel wall-mount bracket).
Less Detail Less Detail
 
Ordering - Includes Options Indicated Below
ADAM 4018
ADAM Remote Data Acquisition Module - 8 Channels of 16-bit A/D with Thermocouple Support
$315.00
ADAM 4018P
ADAM Remote Data Acquisition Module - 8 Channels of 16-bit A/D with Thermocouple Support, Modbus Compliant
$425.00

Driver Software Options
None  
PCL LV
LabVIEW® Controls for Win95/98/200/NT
$0.00
PCL OCX
ActiveX® Controls for Win95/98/NT
$0.00
ADAM OPC
ADAM OPC Server Software for Win98/NT/2000/XP
$225.00

Power Supply Options
None  
CM 243
24VDC Power Supply, 72W, Provides 3A @ 24V from 110/220VAC