| System Bus |
RS-422/485 serial |
| Mounting Configuration |
External module DIN-rail mount Stacking module or daughterboard |
| Isolation |
Isolation, Field-to-Logic |
2500Vrms |
Isolation, Channel-to-Channel |
2500Vrms | |
| Number of I/O Lines |
2 |
| Primary Digital I/O |
Configuration |
2 outputs |
Input/Output Selection |
Fixed | Outputs |
Output Voltage - High (Voh) |
0mV....30V | Output Current Sink, max. |
30mA | Output Current Sink Details |
Power Dissipation: 300mW per channel | |
| Number of User Channels |
2 |
| Counter/Timer Size |
32-bit |
| Input Frequency, max. |
50KHz |
| Gate Width, High, min. |
1s |
| Gate Width, Low, min. |
100ms |
| Counter/Timer Special Features |
- Input Mode: Isolated or Non-isolated
- Isolation Input Level: Logic 0: +1V max, Logic 1: +3.5 ~ 30Vmax
- NON-Isolation Input Level: Programmable
Logic 0:
0 to +5V (default = 0.8V) Logic 1: 0 to +5V (default
= 2.4V)
- Digital Noise Filter: Programmable 2 msec ~ 65 msec
- Alarm: Alarm comparator on each counter
|
|
| Software Included Free with Product |
Diagnostic software Advanced utilities Setup_utility software |
| Operating System Compatibility |
Windows NT 4 |
| Software Compatibility |
DASYLab® GENIDaq DASYLab Lite® LabVIEW® (with optional drivers) |
|
| Connector #1 |
Quantity |
20 |
Type |
Screw terminals | Location |
On module | | Connector & Cabling Details |
Two 10-position screw terminal strips, one on each end of the module |
|
| Construction Material |
Industrial plastic |
|
| Power Consumption (typical) |
2.0W Module requires +10V to +30V DC power, unregulated. |
|
| Other Control Features |
5-digit readout, CH 0 or CH 1 (programmable) |
| Display |
5-digit LED display, shows data value |
|
| Watchdog Timer Included |
Yes |