| System Bus |
RS-422/485 serial |
| Bus Information |
Baud Rate, Max. |
115.2 kbps |
System Bus Details |
Designed for a 4-wire connection via 4 screw terminals: Data+, Data-, +10 to 30VDC power, and Ground. | | Mounting Configuration |
Desktop / benchtop Wall-mount External module DIN-rail mount Stacking module or daughterboard |
| Direct Sensor Input |
Thermocouple |
|
| Number of Channels |
8 |
| Differential Channels |
8 |
| A/D Converter Resolution |
16-bit |
| Max. A/D Speed (throughput) |
8Hz |
| Typ. A/D Speed (throughput) |
8Hz |
| Bandwidth |
5.24Hz |
| Cold Junction Compensation |
Independent input channel for CJC |
| Accuracy |
Zero Drift |
±10µV/°C |
| Noise |
CMRR (Common Mode Rejection Ratio) |
86dB @ 50/60Hz |
| Input Protection |
Protected against field voltages to 240Vrms, max. |
|
| Bipolar Input Ranges |
-10V to +10V -5V to +5V -2.5V to +2.5V -1V to +1V -100mV to +100mV -50mV to +50mV -500mV to +500mV -150mV to +150mV -15mV to +15mV |
| Current Input Ranges |
-20 to +20mA |
| Thermocouple Support |
Thermocouple Inputs |
J-type thermocouple K-type thermocouple T-type thermocouple E-type thermocouple R-type thermocouple S-type thermocouple B-type thermocouple N-type thermocouple C-type thermocouple L-type thermocouple M-type thermocouple L-type (DIN 43710) thermocouple |
J-type Range Supported |
-346°F....1400°F
(-210°C....760°C)
| K-type Range Supported |
-454°F....2501.6°F
(-270°C....1372°C)
| T-type Range Supported |
-454°F....752°F
(-270°C....400°C)
| E-type Range Supported |
-454°F....1832°F
(-270°C....1000°C)
| R-type Range Supported |
32°F....3214.4°F
(0°C....1768°C)
| S-type Range Supported |
32°F....3214.4°F
(0°C....1768°C)
| B-type Range Supported |
32°F....3308°F
(0°C....1820°C)
| N-type Range Supported |
-454°F....2372°F
(-270°C....1300°C)
| C-type Range Supported |
32°F....4208°F
(0°C....2320°C)
| L-type Range Supported |
-328°F....1472°F
(-200°C....800°C)
| L-type (DIN 43710) Range Supported |
-328°F....1652°F
(-200°C....900°C)
| M-type Range Supported |
-328°F....212°F
(-200°C....100°C)
| | A/D Range Selection |
Software |
| Input Range Details |
Current input range requires no external resistor, and is selected via jumper for each channel individually. |
| Isolation, Field-to-Logic |
3000VDC |
|
| Software Included - Features |
OCX, DDE, & DDL libraries, DasyLab & ActiveX drivers on CD-ROM |
|
| Connector #1 |
Quantity |
20 |
Type |
Screw terminals as removable (lift-off) terminal strips | Location |
On module | | Connector & Cabling Details |
- 5.08-pitch holes for the terminal blocks
- Two removable 10-terminal screw terminal blocks make wiring and field
maintenance easy: leave your wiring intact while connecting or disconnecting
modules
|
|
| Construction Material |
Impact resistant ABS plastic |
|
| Power Consumption (typical) |
1.2W |
| Power Supply Notes |
Input: +10VDC to +30VDC |
|
| Other Control Features |
Power indicator LED |
|
| Watchdog Timer Included |
Yes |
|
| Width |
2.85"
(72.4mm)
|
| Height |
4.76"
(121mm)
|
| Depth |
1.3"
(33mm)
|
| Dimension Details |
Depth (no DIN rail mtg block installed): 1.3" (33mm) Depth (DIN rail mtg block installed): 1.496" (38mm) |
|
| Weight |
0.3lbs
(136.08g
)
|